Application:
This product is suitable for connecting indoor and outdoor solar photovoltaic system circuits under extreme weather conditions.
Standard:
2PfG 1169/08.2007 (PV1-F)
Structure:
Conductor: Stranded tinned copper wire in accordance with DIN VDE 0295 and IEC 60228 Class 5
Insulation: electron beam cross-linking, low smoke halogen-free flame retardant composite
Sheath: electron beam cross-linked, low smoke halogen-free flame retardant composite, black,red
Electrical performance:
Rated voltage U0/U: 0.6/1 kV AC; 0.9/1.5 kV DC
Maximum allowable AC voltage: 1.8 kV DC (conductor/conductor, ungrounded system, circuit without load)
Insulation resistance: 1000 M Ω - km
Spark test: 6000 Vac (8400 Vdc)
Voltage endurance: 6500 Vac for 5 minutes
Thermal performance:
Indoor temperature: -40 ℃~+90 ℃
Maximum temperature of conductor: IEC/EN 60216-1 120 ℃ (20000h)
Short circuit temperature: 200 ℃/5s
Heat resistance test: EN 60216-2 (temperature+120 ° C)
High temperature pressure test: EN 60811-3-1
Moisture and heat resistance: EN60068-2-78, 85% humidity
Mechanical properties:
Minimum bending radius: 4 × OD (fixed), 5 × OD (flexible)
Dynamic penetration: 2 PfG 1169/08.2007 Appendix F
Slot propagation: 2 PfG 1169/08.2007 Appendix G
Tensile strength and elongation of insulation and sheath: EN 60811
Expected service life: 25 years
CHEMICAL:
Ozone resistance: EN 50396 part 8.1.3 method B
Weathering and UV resistant: HD 605/A1
Ammonia resistant
Good resistance to oil and chemical corrosion
Good wear resistance and aging resistance
Acid and alkali resistance: according to EN 60811-2-1 (oxalic acid&sodium hydroxide)
EC indicators:
This cable complies with CE 2006/95/EC (low voltage regulations) and
RoHS 2002/95/EC (regulations restricting the use of hazardous substances) in European standards
Fire performance:
Flame retardant performance specified in EN 50265-2-1, IEC 60332-1, VDE 0482-332-1-2, DIN EN 60332-1-2
Low smoke performance specified in IEC 61034, EN 50268
Halogen free performance specified in EN 50267-2-1, IEC 60754-1
Low corrosive gases specified in EN 50267-2-2 and IEC 60754-2
Specifications and dimensions:
Number of cores&nominal cross-sectional area | Number of shares/cables diameter |
Nominal Conductor Diameter | Nominal insulation thickness | Nominal Jacket Thickness | Nominal outer diameter | nominal weight |
---|---|---|---|---|---|---|
No. ×mm² | - | mm | mm | mm | mm | kg/km |
1×1.5 | 30/0.25 | 1.58 | 1.14 | 0.82 | 5.4 | 52 |
1×2.5 | 50/0.25 | 2.04 | 1.14 | 0.82 | 5.8 | 67 |
1×4.0 | 56/0.30 | 2.59 | 1.14 | 0.82 | 6.4 | 87 |
1×6.0 | 84/0.30 | 3.17 | 1.14 | 0.82 | 7.0 | 113 |
1×10 | 78/0.40 | 4.07 | 1.52 | 0.82 | 8.6 | 178 |
1×16 | 128/0.40 | 5.22 | 1.52 | 0.82 | 9.8 | 254 |
1×25 | 199/0.40 | 6.51 | 1.52 | 0.82 | 11.1 | 363 |
1×35 | 279/0.40 | 7.71 | 1.52 | 0.82 | 12.3 | 473 |
current carrying capacity:
conductor cross-section | AWG | Maximum conductor resistance at 20 ℃ | current carrying capacity | ||
---|---|---|---|---|---|
Single exposed to the air Root cable |
A single piece exposed on the surface cable |
Several exposed on the surface Adjacent cables | |||
mm² | - | Ω | A | A | A |
1.5 | 16 | 13.7 | 30 | 29 | 24 |
2.5 | 14 | 8.21 | 41 | 39 | 33 |
4 | 12 | 5.09 | 55 | 52 | 44 |
6 | 10 | 3.39 | 70 | 67 | 57 |
10 | 8 | 1.95 | 98 | 93 | 79 |
16 | 6 | 1.24 | 132 | 125 | 107 |
25 | 4 | 0.795 | 176 | 167 | 142 |
35 | 2 | 0.565 | 218 | 207 | 176 |
Conversion coefficient deviating from temperature:
indoor temperature | transform coefficient |
---|---|
Up to 60 | 1.00 |
70 | 0.91 |
80 | 0.82 |
90 | 0.71 |
100 | 0.58 |
110 | 0.41 |
CONTACT US
Shengdong Cable Co., Ltd
Phone:+86 15542446883
Email:alladu0399@gmail.com
Address:713, Unit 52, Beiyi West Road,
Tiexi District,Shenyang City,
Liaoning Province ,China

MESSAGE
CONTACT US
Shengdong Cable Co., Ltd
Phone:+86 15542446883
Email:alladu0399@gmail.com
Address:713, Unit 52, Beiyi West Road, Tiexi District,
Shenyang City, Liaoning Province ,China
MESSAGE