Solar cable


 

Application:

This product is suitable for connecting indoor and outdoor solar photovoltaic system circuits under extreme weather conditions.

Standard:

2PfG 1169/08.2007 (PV1-F)

Structure:

Conductor: Stranded tinned copper wire in accordance with DIN VDE 0295 and IEC 60228 Class 5

Insulation: electron beam cross-linking, low smoke halogen-free flame retardant composite

 

Sheath: electron beam cross-linked, low smoke halogen-free flame retardant composite, black,red

Electrical performance:

Rated voltage U0/U: 0.6/1 kV AC;  0.9/1.5 kV DC

Maximum allowable AC voltage: 1.8 kV DC (conductor/conductor, ungrounded system, circuit without load)

Insulation resistance: 1000 M Ω - km

Spark test: 6000 Vac (8400 Vdc)

 

Voltage endurance: 6500 Vac for 5 minutes

Thermal performance

Indoor temperature: -40 ℃~+90 ℃

Maximum temperature of conductor: IEC/EN 60216-1 120 ℃ (20000h)

Short circuit temperature: 200 ℃/5s

Heat resistance test: EN 60216-2 (temperature+120 ° C)

High temperature pressure test: EN 60811-3-1

 

Moisture and heat resistance: EN60068-2-78, 85% humidity

Mechanical properties:

Minimum bending radius: 4 × OD (fixed), 5 × OD (flexible)

Dynamic penetration: 2 PfG 1169/08.2007 Appendix F

Slot propagation: 2 PfG 1169/08.2007 Appendix G

Tensile strength and elongation of insulation and sheath: EN 60811

 

Expected service life: 25 years

CHEMICAL:

Ozone resistance: EN 50396 part 8.1.3 method B

Weathering and UV resistant: HD 605/A1

Ammonia resistant

Good resistance to oil and chemical corrosion

Good wear resistance and aging resistance

 

Acid and alkali resistance: according to EN 60811-2-1 (oxalic acid&sodium hydroxide)

EC indicators:

This cable complies with CE 2006/95/EC (low voltage regulations) and

RoHS 2002/95/EC (regulations restricting the use of hazardous substances) in European standards

Fire performance:

Flame retardant performance specified in EN 50265-2-1, IEC 60332-1, VDE 0482-332-1-2, DIN EN 60332-1-2

Low smoke performance specified in IEC 61034, EN 50268

Halogen free performance specified in EN 50267-2-1, IEC 60754-1

 

Low corrosive gases specified in EN 50267-2-2 and IEC 60754-2

Specifications and dimensions:

Number of cores&nominal cross-sectional area Number of shares/cables
diameter
Nominal Conductor Diameter Nominal insulation thickness Nominal Jacket Thickness  Nominal outer diameter nominal weight
No. ×mm² - mm mm mm mm kg/km
1×1.5 30/0.25 1.58 1.14 0.82 5.4 52
1×2.5 50/0.25 2.04 1.14 0.82 5.8 67
1×4.0 56/0.30 2.59 1.14 0.82 6.4 87
1×6.0 84/0.30 3.17 1.14 0.82 7.0 113
1×10 78/0.40 4.07 1.52 0.82 8.6 178
1×16 128/0.40 5.22 1.52 0.82 9.8 254
1×25 199/0.40 6.51 1.52 0.82 11.1 363
1×35 279/0.40 7.71 1.52 0.82 12.3 473


current carrying capacity:

 

conductor cross-section AWG Maximum conductor resistance at 20 ℃ current carrying capacity

Single exposed to the air 

Root cable

A single piece exposed on the surface cable

Several exposed on the surface Adjacent cables
mm² - Ω A A A
1.5 16 13.7 30 29 24
2.5 14 8.21 41 39 33
4 12 5.09 55 52 44
6 10 3.39 70 67 57
10 8 1.95 98 93 79
16 6 1.24 132 125 107
25 4 0.795 176 167 142
35 2 0.565 218 207 176

Conversion coefficient deviating from temperature:

indoor temperature transform coefficient
Up to 60 1.00
70 0.91
80 0.82
90 0.71
100 0.58
110 0.41

 

 

CONTACT US

Shengdong Cable Co., Ltd

Phone:+86 15542446883
Email:alladu0399@gmail.com
Address:713, Unit 52, Beiyi West Road,
Tiexi District,Shenyang City,
Liaoning Province ,China

Image

WhatsApp

MESSAGE

请填写必需的字段。
请填写必需的字段。
请填写必需的字段。

CONTACT US

Shengdong Cable Co., Ltd

Phone:+86 15542446883
Email:alladu0399@gmail.com
Address:713, Unit 52, Beiyi West Road, Tiexi District,
Shenyang City, Liaoning Province ,China

MESSAGE

请填写必需的字段。
请填写必需的字段。
请填写必需的字段。
Image

WhatsApp